FA-1000 SERIES AUXILIARY MODULES
RM-1008A Eight Relay Circuit Module
The RM-1008A Eight Relay Circuit Module provides
eight programable Form C relays. Each relay is
rated for 28 VDC @ 1 Amp max. Each relay is
annunciated for conguration on the front display
board of the MCC-1024-6 or MCC-1024-12 Main
Chassis or ECH-1048 Expander Chassis. The RM-
1008A Relay Adder Module comes with removeable
terminal blocks for easy wiring and servicing. The
module connects via cable to the board on the main
or expander chassis. The RM-1008A also mounts in
the FX-2000 main and expander chassis.
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specications and models and also to discontinue models.
The FA-1000 Series Microprocessor Based Fire Alarm System can be congured to meet virtually any
requirements. To facilitate this exibility, the panel has a number of add-on modules which allow the system to
perform certain functions. The following modules have been designed to adapt the system to suit the particular
requirements of a building.
PR-300 Polarity Reversal & City Tie Module
The PR-300 Polarity Reversal & City Tie Module
allows connection to two different types of monitoring
systems. The City Tie provides an output of 24 VDC
at 210 mA max. The module supervises the City Tie
connection and will provide a system trouble if not
connected. A terminating resistor is supplied with the
module. The Polarity Reversal provides a 24 VDC
output for normal condition and a polarity reverse 24
VDC output for alarm. The module is also capable
of transmitting a system trouble “Zero Volts.” This
option is jumper selectable. The output current is
limited to 8 mA.
5624
NOT TO BE USED FOR INSTALLATION PURPOSES.
S7010 S7010
MEA
approved
7135-1477:106
313-97-E
CATALOG NUMBER
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - CATALOG NUMBER

FA-1000 SERIES AUXILIARY MODULESRM-1008A Eight Relay Circuit ModuleThe RM-1008A Eight Relay Circuit Module provides eight programable Form C rela

Seite 2 - Ordering Information

Canada25 Interchange WayVaughan, Ontario L4K 5W3Telephone: (905) 660-4655Fax: (905) 660-4113Web page: http://www.mircom.com Email: mail@mir

Kommentare zu diesen Handbüchern

Keine Kommentare