FA-300-6L Installation and Operation Manual
45
4. Set password (Command-Menu)
5. View Event Log (Command-Menu)
The event log looks the same as the normal event queue. Pressing the “INFO” key has the same effect that it does
in the event queue. The illustration below provides an example of how the “INFO” key works and shows the CFG-
300 LCD Configuration tool display.
There are a maximum of 200 recent events saved in the event log. If the number of events goes beyond 200, the
oldest event is overwritten by the most recent one.
Note: Refer to How to Use the Keypad to Program the FA-300 on page 34 for detailed instructions on
making menu selections.
If the passcode does not match, the
following message appears and the
system exit to the main menu
If the passcode is OK the following
message appears and exits to the main
menu
1111 -> Default
Use this function to change the
pass-code. The minimum
number of digits is 4 and the
maximum is 10. Only numeric
digits are allowed.
Enter new passcode
[ ]
Re-enter passcode
[ ]
invalid passcode
Passcode updated
EAST LOBBY ENTRANCE
OPEN TRB 01/09
VERIFIED ALARM Z-01
2002/10/22 11:45.AM
ZONE
Message
EVENT
01 of 09
Process
Type
Physical
Zone No.
DATE
TIME
"INFO" Key
EVENT
type
ZONE
Message
EVENT
type
“INFO” KEY
Process
Type
Physical
Zone No.
Time